A Class 150 flange does not have a universal pressure limit of 150 psi. Its pressure rating depends on the material group and metal temperature specified in ASME B16.5. A flange that meets the pressure requirement at ambient temperature can become unsuitable at a higher design temperature without any change in size, class, or dimensions.
Products described as “ANSI B16 5 pipe flanges” are generally being referenced by a legacy designation; the governing standard is ASME B16.5. A defensible selection requires the specified edition, the exact material designation, the applicable pressure–temperature table, and the relevant notes—not simply a class marking or a supplier’s dimensional drawing.
ASME B16.5 covers pressure–temperature ratings, materials, dimensions, tolerances, marking, testing, and related requirements for pipe flanges and flanged fittings within its scope. It includes Classes 150, 300, 400, 600, 900, 1500, and 2500, with size availability dependent on class. The overall nominal size range extends from NPS 1/2 through NPS 24; not every class covers that full range.
The class number identifies a standardized rating category and associated dimensional requirements. It is not a pressure expressed in psi, bar, or any other unit. Descriptions such as “150-pound flange” are commercial shorthand, not a reliable basis for engineering evaluation.
For a given material group, allowable pressure generally decreases as temperature increases. Different material groups can also have different ratings at the same class and temperature. Consequently, neither “Class 300” nor “stainless steel” supplies enough information to determine an allowable working pressure.
The pressure–temperature rating is also distinct from the pressure capability of the completed piping system. Pipe wall thickness, valves, branch connections, bolting, gasket selection, and external loading can introduce separate limitations.
The correct starting point is the material specification and grade shown in the purchase specification, component marking, and material documentation. “Carbon steel,” “316 stainless,” or “forged alloy steel” is insufficient when selecting the governing table.
ASME B16.5 assigns listed materials to material groups. The pressure–temperature tables correspond to these groups. ASTM A105 forged carbon steel, for example, is associated with Material Group 1.1. Other carbon steels, alloy steels, and stainless grades must be traced through their own entries rather than assumed to share the same rating.
Material product form matters. A forged flange specified to ASTM A182 and a cast flanged component specified to ASTM A351 do not become interchangeable merely because their alloy descriptions appear similar. The standard’s material listing establishes the relevant grouping and any qualifications attached to that listing.
Grade suffixes, heat-treatment requirements, and notes can also affect applicability. A low-carbon stainless grade should not automatically inherit the rating of a related higher-carbon grade. Dual-certified material must be evaluated against the actual certification and applicable standard provisions, not treated as permission to choose whichever table gives the higher pressure.
A reliable lookup therefore preserves this chain:
Material specification and grade → B16.5 material group → applicable rating table → class column → temperature row → governing notes.
If the supplied grade is not listed, a similar chemical composition does not establish B16.5 rating eligibility. An alternative design or qualification route must be resolved under the governing construction code and project requirements.
Once the material group is established, use the corresponding pressure–temperature table in the contractually specified edition. Confirm the unit system before extracting a value. B16.5 provides ratings in metric and U.S. customary units; the two systems should be used independently rather than mixed within a calculation.
The temperature used for the rating is the pressure-containing component’s metal temperature. The process-fluid temperature is not automatically the correct value, although it may be an appropriate design basis in many services. Where a different metal temperature is used, that choice needs engineering justification under the applicable piping code.
The table intersection gives the maximum rated working pressure for that material group, class, and temperature, subject to the standard’s conditions. Pressure values are gauge pressures. A process specification expressed in absolute pressure must be converted to a consistent pressure basis before comparison.

The following limited example shows the reading method using commonly published Group 1.1 Class 150 values. It is not a substitute for the governing edition’s complete table and notes.
These values apply to the identified material group and class. They must not be transferred to another material group, extended beyond the listed temperature range, or treated as the pressure rating of every component in the line.
ASME B16.5 permits linear interpolation between listed temperatures for pressure–temperature ratings. For an intermediate temperature, calculate between the two adjacent table entries rather than selecting the lower-temperature row, which would overstate the available rating.
Using the example above, the interpolated Class 150 rating at 350°F is:
P350 = 230 + [(350 − 300) ÷ (400 − 300)] × (200 − 230) = 215 psig.
A specified design condition of 210 psig at 350°F would therefore satisfy this particular table comparison, assuming the material, edition, notes, and other requirements are applicable. The same flange would not satisfy 210 psig at 400°F, where the illustrated rating is 200 psig.
The 5 psi difference in the first comparison is not an allowance for unexamined pressure excursions, uncertain temperatures, or external loads. Those conditions must be addressed separately. A flange does not acquire additional operating capacity because its pressure test was conducted above its working-pressure rating.
Interpolation must remain within the table’s valid range and respect any notes or boundaries. Do not extend a downward pressure curve beyond the highest listed temperature. At low temperatures, do not infer increasing pressure capacity by extrapolating above the rating at the lowest tabulated temperature.
A flange evaluation should use the applicable coincident pressure and temperature conditions, not merely the normal operating point. Startup, shutdown, steam-out, regeneration, blocked-in heating, and other defined operating cases may produce a more demanding combination.
Consider a line operating at 180 psig and 300°F but specified for 210 psig at 400°F. The normal condition is below the illustrative Group 1.1 Class 150 rating, while the design condition exceeds it. Selecting the flange from normal operation alone would produce the wrong result.
Conversely, the highest pressure and highest temperature may arise in separate, noncoincident cases. The applicable code and project design basis determine whether they must be combined or evaluated as distinct conditions. That decision should be documented rather than inferred from a process summary.
A higher class may resolve a pressure–temperature shortfall, but it also changes connection requirements. A Class 300 flange is not a direct bolt-on replacement for a Class 150 flange of the same nominal size. Mating equipment, dimensions, bolting, gasket arrangements, and nozzle loads require review.
A numerical comparison is incomplete without the notes associated with the material listing and rating table. Depending on the material and service, these can address temperature restrictions, heat treatment, prolonged exposure, or other conditions affecting applicability.
High-temperature acceptability is not established solely by finding a pressure value in a table. Material stability, creep-related behavior, oxidation, and service-specific degradation may require additional assessment under the governing code and material specification.
Low-temperature service requires a separate distinction: pressure capacity is not the same as resistance to brittle fracture. A satisfactory pressure comparison does not establish adequate toughness. Minimum design metal temperature, thickness, material condition, impact-testing requirements, and applicable code exemptions must be evaluated independently.
Corrosion creates another separate obligation. The rating table does not establish compatibility with the process fluid or predict service life. Material selection, corrosion allowance where applicable, erosion, and inspection requirements remain part of the piping design.
A B16.5 rating is not an unconditional guarantee of leak-tight performance. The completed joint depends on compatible mating components, appropriate bolting and gaskets, correct assembly, and acceptable loading.
For a joint between dissimilar materials, evaluate both flanges at the applicable temperatures. The lower applicable rating governs the pressure comparison, but satisfying that comparison alone does not establish gasket, bolting, or facing compatibility.
Hydrostatic testing also needs separate treatment. Test pressures and temperatures are governed by the applicable standard and piping code provisions. A successful short-duration test does not authorize continuous operation above the pressure–temperature rating.
A useful technical approval records the B16.5 edition, material specification and grade, material group, table reference, pressure class, evaluated temperature, rated pressure, and governing design condition. Any interpolation should remain visible in the calculation record.
Supporting documentation should connect the supplied component to that basis: material certificates, heat identification, component markings, dimensional verification, and specified inspection or test records. A generic supplier rating chart is useful for screening, but it cannot resolve missing material identity or omitted table notes.
ASME B16.5 is a product standard, not a standalone certification scheme proving that a particular piping system is safe for service. A supplier declaration of conformity does not replace material traceability, required inspection, or design verification under the applicable piping code.
The decisive question is therefore not whether a flange is labeled Class 150 or Class 300. It is whether the documented material, at the specified metal temperature and coincident pressure, satisfies the governing rating table and all applicable joint and code requirements. That is the distinction between a catalog match and a technically supportable flange selection.